1.1 This test method measures air-leakage rates through a building envelope under controlled pressurization and de-pressurization.

1.2 This test method is applicable to small temperature differentials and low-wind pressure differential, therefore strong winds and large indoor-outdoor temperature differentials shall be avoided.

1.3 This test method is intended to quantify the air tightness of a building envelope. This test method does not measure air change rate or air leakage rate under normal weather conditions and building operation.

Note 1See Test Method E741 to directly measure air-change rates using the tracer gas dilution method

1.4 This test method is intended to be used for measuring the air tightness of building envelopes of single-zone buildings. For the purpose of this test method, many multi-zone buildings can be treated as single-zone buildings by opening interior doors or by inducing equal pressures in adjacent zones.

1.5 Only metric SI units of measurement are used in this standard. If a value for measurement is followed by a value in other units in parentheses, the second value may be approximate. The first stated value is the requirement.

1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazard statements see Section 7.

PDF Catalog

PDF Pages PDF Title
1 Scope
Referenced Documents
Terminology
2 Summary of Test Method
Significance and Use
Apparatus
Hazards
Procedure
TABLE 1
3 Data Analysis and Calculations
FIG. 1
4 Report
FIG. 2
5 Precision and Bias
Keywords
A1. PROCEDURE FOR ESTIMATING PRECISION ERRORS IN DERIVED QUANTITIES
A1.1
6 X1. DEPENDENCE OF AIR DENSITY AND VISCOSITY ON TEMPERATURE AND BAROMETRIC PRESSURE (ELEVATION)
X1.1
TABLE A1.1
7 X2. EXAMPLE CALCULATIONS
X2.1 Introduction
X2.2 Site Data
X2.3 Checking Test Limits
X2.4 Pressurization Data
TABLE X2.1
TABLE X2.2
8 X2.5 Depressurization Data
TABLE X2.3
TABLE X2.4
9 X2.6 Combined Pressurization and Depressurization Data
X2.7 Estimates of Confidence Limits
TABLE X2.5
TABLE X2.6